Chapter10 Alarm Monitoring and M anagement
Alarm Profiles
10.3.1 Creating and Modifying Alarm Profiles
Alarm profiles are created at the network view using the Provisioning > Alarm Profiles tabs
(Figure10-7.) A default alarm profile (in the Default column) is pre-provisioned for every alarm. After
loading the Default profile on the node, you can use the C lone fea ture to cre ate ne w pr ofil es ba se d on
the default alarm profile. After the new profile is created, the Alarm Profiles tab shows the default profile
and the new profile.
Figure10-7 Alarm profiles screen showing the default profiles of the listed alarms

Procedure: Create an Alarm Profile

Step 1 Display the CTC network view.
Step 2 Click the Provisioning > Alarm Profiles tabs.
Step 3 Click Load.
Step 4 Highlight the node name you are logged into under Node Names and highlight Default under Profile
Names.
Step 5 Click OK.
Step 6 Right-click anywhere in the Default column to display the Profile Editing menu.
Step 7 Choose Clone from the menu. (You can also clone any other profiles that appear under the Available
button, except Inherited.)
Step 8 In the Clone Profile Default dialog box, enter a name in New Profile Name.