Advanced Operations

6.3.3.11 Function set to SYSTEM ERROR working mode

SYSTEM ERROR

 

 

Default value: DISABLED

 

WARNING LIST

ENABLED: Monitors the internal warning bits of every probe.

 

 

DISABLED: Monitoring is disabled.

 

 

 

 

 

Default value: DISABLED

 

ERROR LIST

ENABLED: Monitors the internal error bits of every probe.

 

 

DISABLED: Monitoring is disabled.

 

 

 

 

 

Default value: DISABLED

 

SENSOR MISSING

Monitors the connection of every connected probe.

 

ENABLED: Monitoring is active.

 

 

 

 

DISABLED: Monitoring is not active.

 

 

 

 

ON DELAY

Default value: 5 seconds

 

(0 s–999 s)

Sets a delay for the relay to turn on.

 

 

 

 

OFF DELAY

Default value: 5 seconds

 

(0 s–999 s)

Sets a delay for the relay to turn off.

 

 

 

 

 

Default value: OFF

 

LOG INTERVAL

Sets the interval for logging the displayed value into the data logger.

 

 

Options: OFF, 5 min, 10 min, 15 min, 20 min, 30 min.

 

 

 

108

Page 110
Image 110
Hach sc1000 user manual Function set to System Error working mode, 108, Sensor Missing