6F3B0250

6. Programming Information

The followings are examples of index modifications.

I

RW10

J

D0201×D0200

When I = 0, it designates RW10. When I = 1, it designates RW11. When I = -1, it designates RW09. When I = 10, it designates RW20. When I = -10, it designates RW00.

When J = 0, it designates D0201×D0200. When J = 1, it designates D0202×D0201. When J = 2, it designates D0203×D0202. When J = -1, it designates D0200×D0199. When J = -2, it designates D0199×D0198.

 

! CAUTION

Be careful that the registers do not exceed the address range by the index

 

 

 

 

 

modification. The address range is not checked by the T1/T1S.

 

 

 

 

 

NOTE

Substitutions of values into index registers and index modifications can be used any times in a program. Normally, the program will be easier to see if a value substitution into an index register is positioned immediately before the index modification.