6F3B0250

Basic Hardware and Function 259

7. Instructions

FUN 236 XFER Expanded data transfer

Expression
Input -[
A
XFER
B
®
C
]- Output
Function

When the input is ON, data block transfer is per formed bet ween the source which is indirectly

designated by

A

and

A+1

and the destination which is indirectly designat ed by

C

and

C+1

. The

transfer size (number of words) is designated by

B

.

The tr ansfer size is 1 to 256 words. (except for writing into EEPROM)

Data transfer between the following objects are available.

· CPU regist er (RW or D) « EEPROM (D register )

· CPU regist er (RW or D) « T1S RS-485 port ( T1S only)

Execution condition
Input Operation Output ERF
OFF No execution OFF -
ON Normal execution ON -
When error is occurred (see Note) ON Set
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Source
parameter ÖÖÖÖÖÖÖ
B
Transfer size ÖÖÖÖÖÖÖ
C
Destination
parameter ÖÖÖÖÖÖ

Parameters

Source parameter Transfer size and status Destination parameter
A
Type
B
Transfer size
C
Type
A+1
Leadin
g
address
B+1
Status fla
g
for RS-485 port
C+1
Leadin
g
address
B+2
(max. 2 words)
Re
g
ister type Type code Leadin
g
address Transfer size
RW re
g
ister (RAM) H0003 0 to 63 (T1)
0 to 255 (T1S) 1 to 64 (T1)
1 to 256 (T1S)
D re
g
ister (RAM) H0004 0 to 1023 (T1)
0 to 4095 (T1S) 1 to 256
D re
g
ister (EEPROM) H0020 0 to 511 (T1)
0 to 2047 (T1S) 1 to 16 (if destination, T1)
1 to 32 (if destination,T1S)
1 to 256 (if source)
T1S RS-485 port H0030 0 (fixed) 1 to 256