6F3B0250

7. Instructions

B+8 Initial status STS

F

 

 

C

8

4

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Initial operation mode 00 : Manual mode

01 : Auto mode

10 : Cascade mode

11 : (Reserve)

Direct / reverse selection

 

 

0 : Direct

 

 

 

1 : Reverse

B+9

MV upper limit MH (-25.00 to 125.00 %)

Data range: -2500 to 12500

B+10

MV lower limit ML (-25.00 to 125.00 %)

Data range: -2500 to 12500

B+11

MV differential limit DMV (0.00 to 100.00 %/Dt)

Data range:

0 to 10000

B+12

Control interval setting n (1 to 32767 times)

Data range:

1 to 32767

 

Executes PID every n scan. Therefore, control interval Dt = n ´ constant scan interval

 

(It is treated as n = 1 when n £ 0)

 

 

C

Manipulation value MV (-25.00 to 125.00 %)

Data range: -2500 to 12500

C+1

 

 

 

:Internal work area

C+9

Operation

1. When the instruction input is OFF:

 

Initializes the PID3 instruction.

A+5 bit 0, 1 ¬ B+8 bit 0, 1

Operation mode is set as specified by B+8.

Auto mode SV is set as specified by B+4.

ASV ¬ ISV

Manual mode MV is set as current MV.

MMV ¬ MV

Internal calculation data is initialized.

 

MV remains unchanged.

 

2.When the instruction input is ON:

Executes PID calculation every n scan which is specified by B+12. The following operation modes are available according to the setting of A+5.

·Auto mode

This is a normal PID control mode with ASV as set value.

Set value differential limit DSV, manipulation value upper/lower limit MH/ML and differential limit DMV are effective.

Bump-less changing from auto mode to manual mode is available. (Manual mode manipulation value MMV is over-written by current MV automatically. MMV ¬ MV)

240 T1/T1S User’s Manual