6F3B0250

6. Programming Information

6.3 Real-time clock/calendar (T1S only)

The T1S is equipped with the real-time clock/calendar for year, month, day, day of the week, hour, minute, and second.

These data are stored in the special registers SW07 to SW13 by 2-digit BCD format as follows.

Register

Function

Data

SW07

Year

1998 = H0098, 1999 = H0099, 2000 = H0000, 2001 = H0001, ...

SW08

Month

Jan. = H0001, Feb. = H0002, Mar. = H0003, ... Dec. = H0012

SW09

Day

1st = H0001, 2nd = H0002, 3rd = H0003, ... 31st = H0031

SW10

Hour

H0000, H0001, H0002, ... H0022, H0023

SW11

Minute

H0000, H0001, H0002, ... H0058, H0059

SW12

Second

H0000, H0001, H0002, ... H0058, H0059

SW13

Week

Sun. = H0000, Mon. = H0001, Tue. = H0002, ... Sat. = H0006

Program example:

In the following circuit, output Y030 turns ON for 1 minute at every Sunday 6 pm.

(H0018)

Clock/calendar back-up:

The clock/calendar continues updating even while the power to the T1S is off by built-in capacitor. Its buck-up period is as follows.

Temperature

Expected value

Guarantee value

25 °C

300 hours

168 hours

40 °C

144 hours

72 hours

In the T1S, the validity of the clock/calendar is checked. If the data is not valid by excess power off period, special relay S00A is set to ON. Therefore, when the clock/calendar is used, it is recommended to check the status of S00A in the user program.

Setting the clock/calendar:

To set the clock/calendar data, the following 2 ways are available. In both cases, the week data is automatically calculated.

(a)Setting the clock/calendar data on the system information screen of the programming tool.

(2) Using the Calendar Set instruction (CLND) in the user program.