6F3B0250

7. Instructions

Transitional contact (Rising edge)

Expression

Input Output

Function

When the input at last scan is OFF and the input at this scan is ON, the output is turned ON. This instruction is used to detect the input changing from OFF to ON.

Execution condition

Input

Operation

Output

OFF

Regardless of the input state at last scan

OFF

ON

When the input state at last scan is OFF

ON

 

When the input state at last scan is ON

OFF

Operand

No operand is required.

Example

Coil Y022 comes ON for only 1 scan when the device X000 comes ON.

X000

Y022

1 scan time 1 scan time

Note

· In case of T1, the maximum usable number in a program is 512. (

and

total)

·In case of T1S, the maximum usable number in a program is 2048.

( P N (P) (N) total)

Basic Hardware and Function 137