6F3B0250

1. System Configuration

1.7 T1S communication function

The T1S has an RS-485 muiti-purpose communication port. This port can work independent of the programmer port.

By using this communication port, one of the following three communication modes is available, computer link mode, data link mode and free ASCII mode.

For details of these functions, refer to the separate manual “T1/T1S User’s Manual - Communication Function -”.

Item

Computer link

Free ASCII

Data link

Interface

Conforms to RS-458 (4-wire or 2-wire)

 

Transmission system

Half-duplex

 

 

 

Synchronization

Start-stop system (asynchronous)

 

Transmission code

ASCII/binary

ASCII

Binary

Transmission speed

300, 600, 1200, 2400, 4800, 9600, or

19200 bps (fixed)

 

19200 bps

 

 

 

Transmission distance

1 km max.

 

 

 

Framing

Start bit:

1 bit

 

Special

 

Data bits:

7 or 8 bits

 

 

Parity:

Odd, even, or none

 

 

Stop bit:

1 or 2 bits

 

Protocol

T-series

 

User defined

Special

 

computer link

ASCII messages

 

 

(ASCII),

 

 

 

 

Programmer

 

 

 

(binary)

 

 

 

Link configuration

1-to-N

 

N/A

1-to-1

Transmission delay

0 to 300 ms

 

N/A

N/A

option

 

 

 

 

Computer link mode

T-series computer link protocol can be used in this mode. A maximum of 32 T1Ss can be connected to a master computer.

By using this mode, all the T1S’s data can be accessed by a master computer. The T-series PLC programming software (T-PDS) can also be used in this configuration.

Master Computer

RS-485 (1 km max.)

T1

T1

T1

T1

Max. 32 T1Ss