10. Troubleshooting

Error message and related information

Special

Meaning and countermeasures

Event

Info 1

Info 2

Info 3

device

 

Illegal inst

Program

Address

 

S006

An illegal instruction has been detected in the

 

type -

in the

 

S030

program. (Error down)

 

block No.

block

 

S060

Reload the program and execute EEPROM

 

 

 

 

 

write operation again.

Illegal sys intrpt

Interrupt

Interrupt

 

 

Unregistered interrupt has occurred. (No

 

address 1

address 2

 

 

error down)

 

 

 

 

 

If the error occurs frequently, replace the unit.

Invalid Fun inst

Program

Address

Fun No.

 

A function instruction which is not supported

 

type -

in the

 

 

by the T1/T1S is programmed. (Error down)

 

block No.

block

 

 

Correct the program.

Invalid program

Program

 

 

 

A basic ladder instruction which is not

 

type -

 

 

 

supported by the T1/T1S is programmed.

 

block No.

 

 

 

(Error down)

 

 

 

 

 

Correct the program.

 

 

 

 

 

SUBR instruction is not programmed before

 

 

 

 

 

RET instruction. (Error down)

 

 

 

 

 

Correct the program.

 

 

 

 

 

An abnormality is detected in the program

 

 

 

 

 

management information. (Error down)

 

 

 

 

 

Reload the program and execute EEPROM

 

 

 

 

 

write operation again.

Loop nesting error

Program

Address

 

 

A FOR-NEXT loop is programmed inside

 

type -

in the

 

 

other FOR-NEXT loop. (Error down)

 

block No.

block

 

 

Correct the program.

Memory full

 

 

 

 

The program exceeds the executable

 

 

 

 

 

memory capacity. (Error down)

 

 

 

 

 

Reduce the program steps.

No END/IRET error

Program

Address

 

 

The END instruction is not programmed in

 

type -

in the

 

 

the main program or in the sub-program.

 

block No.

block

 

 

(Error down)

 

 

 

 

 

Correct the program.

 

 

 

 

 

The IRET instruction is not programmed in

 

 

 

 

 

the interrupt program. (Error down)

 

 

 

 

 

Correct the program.

No RET error

Program

Address

Sub-r No.

 

The RET instruction is not programmed in the

 

type -

in the

 

 

subroutine program. (Error down)

 

block No.

block

 

 

Correct the program.

No sub-r entry

Program

Address

Sub-r No.

 

The subroutine corresponding to CALL

 

type -

in the

 

 

instruction is not programmed. (Error down)

 

block No.

block

 

 

Correct the program.

302 T1/T1S User’s Manual

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Page 304
Image 304
Toshiba PROSEC T1 T1S, 6F3B0250 user manual 302 T1/T1S User’s Manual