6F3B0250

7. Instructions

FUN 074

SR

Shift register

Expression

Data input

-

 

D SR

 

 

- Output

 

Q

Shift input

-

 

S

(n)

 

 

 

Enable input

-

 

E

 

A

 

 

 

 

 

 

 

 

 

Function

While the enable input is ON, this instruction shifts the data of the bit table, size n starting with A,

1 bit to the left (upper address direction) when the shift input is ON. The state of the data input is stored in A. The pushed out bit state is stored in the carry flag (CF = S050).

When the enable input is OFF, all bits in the table and the carry flag are reset to OFF.

Execution condition

Enable

Operation

 

Output

CF

input

 

 

 

 

OFF

Resets all bits in the bit table

 

OFF

Reset

ON

When the shift input is ON

Shift execution

Last bit

Set or reset

 

When the shift input is OFF

No execution

state

-

Operand

 

Name

 

 

Device

 

 

 

 

 

 

Register

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

I

J

K

 

 

A

Leading device

 

Ö

Ö

Ö

 

 

 

 

 

 

 

 

 

 

 

 

 

 

n

Device size

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 - 64

 

Example

32 devices starting with R100 (R100 to R11F) is specified as a shift register.

When R010 is OFF, the data of the shift register is reset to 0. (R100 to R11F are reset to OFF) The carry flag (CF = S050) is also reset to OFF.

While R010 is ON, the data of the shift register is shifted 1 bit to the upper address direction when X009 is changed from OFF to ON. At the same time, the state of X008 is stored in the leading bit (R100).

The output (R011) indicates the state of the last bit (R11F).