6F3B0250

7. Instructions

The figure below shows an operation example. (When X009 is changed from OFF to ON)

CF

 

R11F R11E R11D R11C

 

 

 

1

0

0

1

 

R103 R102 R101 R100

0

0

1

1

X008

0

1

0

0

1

0

1

1

0

Shift result

R011 is turned OFF

Note

·When the shift input is ON, the shift operation is performed every scan. Use a transitional contact for the shift input to detect the state changing.

·For the data input and the shift input, direct linking to a connecting point is not allowed. In this case, insert a dummy contact (always ON special device = S04F, etc.) just before the input.

D SR Q

S(n)

EA

( )

Not allowed

Dummy contact

( )

D SR Q

S (n)

E A

Allowed

Basic Hardware and Function 187