7. Instructions
<Transmitting>
When the instruction input is ON, one set of message which is stored in the source table (from start character to the trailing code) is transmitted through the
The instruction input must be kept ON until the transmitting operation is complete.
Example
| Source designation | ||
D0010 | H00 |
| H04 |
D0011 |
| 00500 |
D0500 (CPU register)
Transfer size
D0012 00012
D0013 Execution status
Destination designation
D0015 H00 H30
D0016 00000
T1S
When R0001 is ON, one set of message (ended by the trailing code) stored in the range of D0500 to D0511 (12 words) is transmitted through the
Execution status:H0000 ... Normal complete
H0001 ... During transmitting the message
H0002 ... Communication busy
H0003 ... During the reset operation
H0004 ... Send
H0005 ... Send message length error (no trailing code in the source table)
Baudrate | |
300, 600, 1200 bps | 30 seconds |
2400 bps | 15 seconds |
4800 bps | 7 seconds |
9600 bps | 3 seconds |
19200 bps | 1.5 seconds |
Note
·The XFER instruction is not executed as error in the following cases. In these cases, the instruction error flag (ERF = S051) is set to ON. If the ERF is set to ON once, it remains ON until resetting to OFF by user program.
(1)The leading address for the
(2)Transfer size is out of the range of 1 to 256.
(3)Mode setting of the
(4)This instruction is programmed in the
262 T1/T1S User’s Manual