T1-16 input specifications

Item Specifications
DC input type AC input type
AC power type DC power type
Input type Dry contact input,
current source or
sink
*1
DC input,
current source or
sink
*2
AC input
Number of input
points 8 points (8 points/common) 8 points (8 points/common)
Rated input volta
g
e Supplied from
T1-16
(24 Vdc, ±10 %)
24 Vdc,
+10/-15% 100 - 120 Vac, +10/-15 %,
50/60 Hz
Rated input current 7 mA (at 24 Vdc) 7 mA (at 100 Vac)
ON level Contact close
(max. 1.2 kW)Min. ON
volta
g
e: 15 Vdc Min. ON volta
g
e: 80 Vac
OFF level Contact open
(min. 20 kW)Min. OFF
volta
g
e: 5 Vdc Max. OFF volta
g
e: 30 Vac
ON delay time 0 to 15 ms
*3
25 ms or less + user settin
g
*4
OFF delay time 0 to 15 ms
*3
30 ms or less + user settin
g
*4
Input si
g
nal display LED display for all points, lit at ON, internal lo
g
ic side
External connection Terminal block (fixed), M3.5
Withstand volta
g
e 1500 Vac, 1 minute (between internal and external circuits)
Internal circuit
*1: The input current direction (source or sink) of the dry contact input can be selected by the
internal jumper plug. (Factory setting = current source) Refer to section 3.1.
3 side: current flows from input terminal to (-) terminal (current source)
1 side: current flows from (+) terminal to input terminal (current sink)
*2: The jumper plug of the DC power supply type must be set to 1 side.
*3: The input ON/OFF delay time of the DC input type can be changed by user. The setting range is
0 to 15 ms. (Default value = 10 ms) Refer to section 8.2.
*4: The input ON/OFF delay time of the AC input can be extended by user. The extension setting
range is 0 to 15 ms. (Default value = 10 ms) Resulting the default delay times are 35 ms (ON
delay) and 40 ms (OFF delay). Refer to section 8.2.
LED

+

-

24 Vdc
(AC power type only)
*1
,
*2
13
7
0
LED
C
7
0