6F3B0250
210 T1/T1S User’s Manual
7. Instructions

FUN 110 U=Unsigned equal

Expression
Input -[
A
U=
B
]- Output
Function
When the input is ON, the data of
A
and the data of
B
are compared, and if
A
is equal to
B
, the output
is turned ON.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution
A
=
B
ON
A
¹
B
OFF
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Compared
data ÖÖÖÖÖÖÖÖÖÖ Ö Ö
B
Reference data ÖÖÖÖÖÖÖÖÖÖ Ö Ö
Example
When R00C is O N, the data of D0125 is com par ed with the dat a of D0030, and if the data of
D0125 is equal to t he dat a of D0030, R020 is turned ON.
If t he data of D0125 is 35000 and that of D0020 is 35000, the comparison result is t r ue.
Consequently, R020 is t ur ned O N.
D0125 35000 =D0030 35000 R020 is ON
If t he data of D0125 is 1500 and that of D0020 is 4000, the comparison result is false.
Consequently, R020 is t ur ned O FF.
D0125 1500 ¹D0030 4000 R020 is OFF
Note
· This instr uct ion deals with the dat a as unsigned integer ( 0 t o 65535).
T1S only
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net