8. Special I/O Functions

8.1 Special I/O function overview

The T1/T1S supports the special I/O functions as listed below.

Function name

Function summary

Remarks

Variable input filter

Input filter constant (ON/OFF delay time) can be set by

SW16 setting

constant

 

user program. The setting range is 0 to 15 ms

is necessary to

 

 

(1 ms units). Default value is 10 ms. This function is

use this

 

 

applied for X000 to X007 (8 points as a block).

function. (Note)

High

Single phase

Counts the number of pulses of single phase pulse

Only one

speed

up-counter

train. 2 channels of pulse input are available. The

among these 4

counter

 

countable pulse rate is up to 5 kHz for each channel.

functions can

 

 

Channel 1 ¼ X000 count input, X002 reset input

be selected.

 

 

Channel 2 ¼ X001 count input, X003 reset input

SW16 is used

 

Single phase

Counts the number of pulses in a specified sampling

to select the

 

speed-

time. The sampling time setting is 10 to 1000 ms (10

function.

 

counter

ms units). 2 channels of pulse input are available. The

(Note)

 

 

countable pulse rate is up to 5 kHz for each channel.

 

 

 

Channel 1 ¼ X000 count input

 

 

 

Channel 2 ¼ X001 count input

 

 

Quadrature

Counts the 2-phase pulses whose phases are shifted

 

 

bi-pulse

90° each other. Counts up when phase A precedes,

 

 

counter

and counts down when phase B precedes. The

 

 

 

countable pulse rate is up to 5 kHz.

 

 

 

Phase A ¼ X000

 

 

 

Phase B ¼ X001

 

 

 

Reset ¼¼ X002

 

Interrupt input function

Immediately activates the corresponding I/O interrupt

 

 

 

program when the interrupt input is changed from OFF

 

 

 

to ON (or ON to OFF). 2 points of interrupt input are

 

 

 

available.

 

 

 

X002 ¼ Interrupt 1 (I/O interrupt program #3)

 

 

 

X003 ¼ Interrupt 2 (I/O interrupt program #4)

 

Analog setting function

The value of the analog setting adjuster is converted

No function

 

 

into digital value (0 to 1000) and stored in the SW

selection is

 

 

register. 2 adjusters are provided on the T1/T1S.

required.

 

 

V0 ¼ SW30

 

 

 

V1 ¼ SW31

 

Pulse output function

Variable frequency pulse train can be output. The

Either one

 

 

available pulse rate is 50 to 5000 Hz (1 Hz units).

between these

 

 

Y020 ¼ CW or Pulse (PLS)

2 functions can

 

 

Y021 ¼ CCW or Direction (DIR)

be used.

PWM output function

Variable duty cycle pulse train can be output. The

SW26 is used

 

 

available ON duty setting is 0 to 100 % (1 % units).

to select the

 

 

Y020 ¼ PWM output

function. (Note)

NOTE

The above special I/O functions, except the variable input filter constant and analog setting functions, are available only in the DC input types.

268 T1/T1S User’s Manual

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Page 270
Image 270
Toshiba PROSEC T1 T1S, 6F3B0250 user manual Special I/O Functions, Special I/O function overview