1.System Configuration

1.8Real-time data link system

TOSLINE-F10

TOSLINE-F10 is a high speed data transmission system suited for small points I/O distribution system. By inserting the TOSLINE-F10 remote card (FR112) into the T1- 40/T1-40S, the T1-40/T1-40S can work as a remote station of the TOSLINE-F10 network. On this network, the T1-40/T1-40S sends 1 word data to the master station and receives 1 word data from the master station.

Item

TOSLINE-F10 system specifications

 

High speed mode

Long distance mode

Topology

Bus (terminated at both ends)

Transmission distance

500 m max. (total)

1 km max. (total)

(without repeater)

 

 

Transmission speed

750 kbps

250 kbps

Scan transmission

512 points (32 words) max.

 

capacity

 

 

Scan cycle

7 ms/32 words

12 ms/32 words

Error checking

CRC check

 

NOTE

(1) Refer to the separate “T1 User’s Manual - Option Card and I/O Module - for details of the TOSLINE-F10 remote card (FR112).

(2) Refer to the separate TOSLINE-F10 User’s Manual for details of overall TOSLINE-F10 system.

Typical data link configuration

The figure below shows the typical data link configuration.

Master

computer

T2E

(master)

 

 

 

 

TOSLINE-F10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

T1-40(S)

 

T1-40(S)

 

T1-40(S)

 

T2E

 

RI/O

 

 

 

 

 

 

 

 

 

(remote)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RI/O

RI/O: remote I/O