1. System Configurati on

1.2 Features

Option card support:
The T1-40/T1-40S has two slots for the option card, which is approximately 1/2 the size
of a cr edit car d. The f ollowing eig ht types of the option car ds are available.
· 16 points DC input
· 16 points DC output
· 8 DC inputs + 8 DC outputs
· 1 channel analog input ( 0 t o 5 V/0 to 20 mA)
· 1 channel analog input (±10 V)
· 1 channel analog output ( 0 to 20 mA)
· 1 channel analog output ( ±10 V)
· Field network TOSLINE-F10 r emote
By using the 16 points input and 16 point s output cards, t he T1-40/T 1-40S can control
up to 72 I/O points without enlarging the mounting space.
Built- in high speed counter:
Two single-phase or one quadrature (2-phase) pulses can be counted. The acceptable
pulse rate is up t o 5 kHz. (DC input t ype only)
Built- in analog setti ng adjust ers:
Two analog setting adjusters are provided on the T1/T1S. This allows operator s t o
adjust tim e or other control parameters easily using a screwdriver.
High speed processing:
Sophisticated machine control applications require high speed data manipulations. The
T1/T1S is designed to meet these req uir em ent s.
· 1.4 ms per contact · 2.3 ms per coil
· 4.2 ms per 16-bit t ransfer · 6.5 ms per 16-bit addit ion
The T 1/ T1S also supports int e r r upt input funct ion ( DC input t ype only). This allows
immediate oper at ion independent of program scan.
High performance soft ware:
The T1 offers 17 basic ladder instructions and 76 function instructions. The T1S offers
21 basic ladder instruct ions and 99 function instr uct ions.
Subroutines, I nterrupt functions, Indirect addressing, For/Next loops, Pre- der ivative
real PID, et c. are standard on t he T1/T1S. These funct ions allow the T1/ T1S to be
applied to the most demanding control applications.
Battery-less operation:
The T1/T1S has a standard built-in EEPROM, permitt ing oper ation without need of a
battery. Also, t he variable dat a can be writt en int o and/or read f r om the EEPROM,
providing completely maint enance- free back - up operation.
This function is an important feature for OEMs, because it can elim inat e the need for
changing the battery every few years. The cost of the bat t er y is also eliminat ed.