6F3B0250

3. I/O Application Precautions

3.2 Application precautions for output signals

!WARNING

!CAUTION

Configure emergency stop and safety interlocking circuits outside the T1/T1S. Otherwise, malfunction of the T1/T1S can cause injury or serious accidents

1.Turn on power to the T1/T1S before turning on power to the loads. Failure to do so may cause unexpected behavior of the loads.

2.Configure the external circuit so that the external 24 Vdc power required for the transistor output circuits and power to the loads are switched on/off simultaneously. Also, turn off power to the loads before turning off power to the T1/T1S.

3.Install fuses appropriate to the load current in the external circuits for the outputs. Failure to do so can cause fire in case of load over-current.

(1)2 points of solid-state output

The leading 2 points of output (Y020 and Y021) are solid-state outputs, transistors on the DC input types and triacs on the AC input types.

These solid-state outputs are suited for frequent switching applications.

Note that the specifications of the solid-state outputs and other outputs (relays) are different.

(2)Switching life of output relays

Expected relay life is more than 100,000 electrical cycles at rated maximum voltage and current, and more than 20 million mechanical cycles. The expected contact life (electrical cycles) is shown on the table below.

 

Load voltage

Load

Expected life

 

 

current

(thousand)

AC

110 Vac,

2 A

340

load

COSf = 1

1 A

720

 

 

0.5 A

1,600

 

110 Vac,

2 A

150

 

COSf = 0.7

1 A

320

 

 

0.5 A

700

 

220 Vac,

2 A

220

 

COSf = 1

1 A

500

 

 

0.5 A

1,100

 

220 Vac,

2 A

100

 

COSf = 0.7

1 A

210

 

 

0.5 A

460

 

Load voltage

Load

Expected life

 

 

current

(thousand)

DC

24 Vdc,

2 A

280

load

L/R = 0 ms

1 A

600

 

 

0.5 A

1,300

 

24 Vdc,

2 A

60

 

L/R = 15 ms

1 A

150

 

 

0.5 A

350

 

48 Vdc,

1 A

200

 

L/R = 0 ms

0.5 A

420

 

48 Vdc,

0.5 A

130

 

L/R = 15 ms

0.2A

420

 

110 Vdc,

0.5 A

200

 

L/R = 0 ms

0.2 A

550

 

110 Vdc,

0.2 A

150

 

L/R = 15 ms

0.1 A

350

Basic Hardware and Function 65

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Page 67
Image 67
Toshiba 6F3B0250, PROSEC T1 T1S user manual Application precautions for output signals