6F3B0250
2.Specifications
2.3Functional specifications
| Item |
| ||||
Control method | Stored program, cyclic scan system |
|
| |||
Scan system | Floating scan or constant scan (10 - 200 ms, 10 ms units) | |||||
I/O update | Batch I/O refresh (direct I/O instruction available) |
| ||||
Program memory | RAM (capacitor | |||||
RAM memory back- | 6 hours (25°C) |
|
| 168 hours (25°C) | ||
up |
|
|
|
|
|
|
Program capacity | 2 k steps |
|
| 8 k steps | ||
|
|
|
|
|
| (4 k or 8 k mode) |
Programming | Ladder diagram with function block |
|
| |||
language |
|
|
|
| ||
Instructions | Basic ladder instructions: 17 |
| Basic: 21 | |||
|
|
| Function block instructions: 76 |
| Function: 99 | |
Execution speed | 1.4 ms/contact, 2.3 ms/coil, |
|
| |||
|
|
| 4.2 |
| ||
Program types | 1 main program |
|
|
| ||
|
|
| 1 |
|
| |
|
|
| 1 timer interrupt (interval: 5 to 1000 ms, 5 ms units) |
| ||
|
|
| 4 I/O interrupt |
| ||
|
|
| 16 subroutines (nesting not available) | 256 subroutines | ||
|
|
|
|
|
| (up to 3 levels of |
|
|
|
|
|
| nesting) |
User |
| I/O register | 512 points/32 words (X/XW, Y/YW) |
|
| |
data |
| Auxiliary | 1024 points/64 words (R/RW) |
| 4096 points/ | |
|
| relay |
|
|
| 256 words |
|
|
|
|
|
| (R/RW) |
|
| Special | 1024 points/64 words (S/SW) |
|
| |
|
| relay |
|
|
|
|
|
| Timer | 64 points (T./T), 32 @ 0.01 s, 32 @ 0.1 s | 256 points (T./T) | ||
|
|
|
|
|
| 64 @ 0.01 s, |
|
|
|
|
|
| 192 @ 0.1 s |
|
| Counter | 64 points (C./C) |
|
| 256 points (C./C) |
|
| Data | 1024 words (D) |
|
| 4096 words (D) |
|
| register |
|
|
|
|
|
| Index | 3 words (I, J, K) |
|
|
|
|
| register |
|
|
|
|
I/O capacity | 16 points | 28 points | 40 points (basic) |
| ||
|
|
| (fixed) | (fixed) | + 32 points (option cards) | |
|
|
|
|
| + 16 words (I/O modules) | |
Input |
| DC input | Dry contact input | 24 Vdc input |
|
|
type |
| type (Note) | (AC PS), |
|
|
|
|
|
| 24 Vdc input |
|
|
|
|
|
| (DC PS) |
|
|
|
|
| AC input | 100 - 120 Vac input |
|
| |
|
| type |
|
|
|
|
Output |
| DC input | Relay + transistor (2 points) |
|
| |
type |
| type |
|
|
|
|
|
| AC input | Relay + triac (2 points) |
|
| |
|
| type |
|
|
|
|
I/O terminal block | Fixed | Removable |
|
|
46 T1/T1S User’s Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net