6F3B0250
200 T1/T1S User’s Manual
7. Instructions

FUN 100 <Less than

Expression
Input -[
A
<
B
]- Output
Function
When the input is ON, the data of
A
and the data of
B
are compared, and if
A
is less than
B
, the output
is turned ON.
Execution condition
Input Operation Output
OFF No execution OFF
ON Execution
A
<
B
ON
A
³
B
OFF
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Compared
data ÖÖÖÖÖÖÖÖÖÖ Ö Ö
B
Reference data ÖÖÖÖÖÖÖÖÖÖ Ö Ö
Example
When R00C is O N, the data of D0125 is com par ed with the dat a of D0040, and if the data of
D0125 is less than the data of D0040, R020 is tur ned ON.
If t he data of D0125 is 10 and that of D0040 is 15, the comparison result is t r ue. Consequently,
R020 is turned ON.
D0125 10 <D0040 15 R020 is ON
If the data of D0125 is 0 and that of D0040 is -50, the comparison result is false. Consequently,
R020 is turned OFF.
D0125 0 ³D0040 0 R020 is OFF
Note
· This instr uct ion deals with the dat a as signed integer ( - 32768 to 32767).