6F3B0250

7. Instructions

FUN 100

<

Less than

Expression

Input -[ A < B ]- Output

Function

When the input is ON, the data of A and the data of B are compared, and if A is less than B, the output is turned ON.

Execution condition

Input

 

 

Operation

Output

OFF

No execution

 

 

OFF

ON

Execution

A < B

 

ON

 

 

A ³ B

 

OFF

Operand

 

Name

 

 

Device

 

 

 

 

 

 

Register

 

 

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

I

J

K

 

 

A

Compared

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

 

data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Reference data

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Example

When R00C is ON, the data of D0125 is compared with the data of D0040, and if the data of D0125 is less than the data of D0040, R020 is turned ON.

If the data of D0125 is 10 and that of D0040 is 15, the comparison result is true. Consequently, R020 is turned ON.

D0125

10

<D0040

15

R020 is ON

If the data of D0125 is 0 and that of D0040 is -50, the comparison result is false. Consequently, R020 is turned OFF.

D0125

0

³D0040

0

R020 is OFF

Note

·This instruction deals with the data as signed integer (-32768 to 32767).

200 T1/T1S User’s Manual

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Page 202
Image 202