1. System Configuration

Pulse output / PWM output:

One point of variable frequency pulses (max. 5 kHz) or variable duty pulses can be output. These functions can be used to drive a stepping motor or to simulate an analog output. (DC input type only)

Built-in computer link function:

The T1/T1S’s RS-232C programmer port can accept the computer link protocol (data read/write). This results in easy connection to a higher level computer, an operator interface unit, etc.

The parity setting of the programmer port can be selected either odd or none. The none parity mode is provided especially for telephone modem connection. Using modems, remote programming/monitoring is available.

Real-time control data link network:

By inserting the TOSLINE-F10 remote card (option card) into the T1-40/T1-40S, high speed data link network can be established. In this network, upper T-series PLC model (T2/T2E/T2N or T3/T3H) works as master and up to 16 T1-40/T1-40Ss can be connected as remote. Each T1-40/T1-40S can exchange data with the master through 1 word input and 1 word output. The transmission speed can be selected either 750 kbps or 250 kbps.

T2 Series I/O module interface:

In addition to the option cards, the T1-40/T1-40S has a interface for connecting the T2 Series I/O modules. Up to four modules can be connected to the T1-40/T1-40S. The following I/O modules are available.

·

16 points DC input (DI31)

·

16 points DC output (DO31/DO233P)

·

32 points DC input (DI32)

·

32 points DC output (DO32)

·

64 points DC input (DI235)

·

64 points DC output (DO235)

·

16 points AC input (IN51/IN61)

·

12 points AC output (AC61)

·

8 points isolated relay output (RO62)

·

12 points relay output (RO61)

·

4 channels analog input

·

2 channels analog output

 

(AI21/AI22/AI31/AI32)

 

(AO31/AO22/AO32)

·

1 channel pulse input (PI21)

·

1 axis position control (MC11)

·Communication interface (CF211)

Sampling trace function:

The sampling trace is the function to collect the user specified data every user specified timing (minimum every scan), and to display the collected data on the programmer screen in time chart and/or trend graph format. This function is useful for checking the input signals changing.

The collecting capacities between T1 and T1S are different as follows.

·T1 ..... 1 register - 128 times, or 8 devices - 256 times

·T1S ... 3 registers and 8 devices - 256 times

Basic Hardware and Function 17