6F3B0250

7. Instructions

FUN 113

U<=

Unsigned less than or equal

T1S only

Expression

Input -[ A U<= B ]- Output

Function

When the input is ON, the data of A and the data of B are compared, and if A is less than or equal to B, the output is turned ON.

Execution condition

Input

 

 

Operation

Output

OFF

No execution

 

 

OFF

ON

Execution

A £ B

 

ON

 

 

A > B

 

OFF

Operand

 

Name

 

 

Device

 

 

 

 

 

 

Register

 

 

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

I

J

K

 

 

A

Compared

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

 

data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Reference data

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Example

When R00C is ON, the data of D0125 is compared with the constant data 35000, and if the data of D0125 is less than or equal to 35000, R020 is turned ON.

If the data of D0125 is 35000, the comparison result is true. Consequently, R020 is turned ON.

D0125

35000

£Constant

35000

R020 is ON

If the data of D0125 is 0, the comparison result is false. Consequently, R020 is turned OFF.

D0125

38000

>Constant

35000

R020 is OFF

Note

·This instruction deals with the data as unsigned integer (0 to 65535).