10. Troubleshooting

Error message and related information

Special

Meaning and countermeasures

Event

Info 1

Info 2

Info 3

device

 

Batt voltage drop

 

 

 

S00F

In the power-up initialization, data invalidity of

 

 

 

 

 

RAM (back-up area) has been detected.

 

 

 

 

 

If retentive registers are used, these validity

 

 

 

 

 

are not guaranteed. (No error down)

Boundary error

Program

Address

FUN No.

 

The register of index modification is other

 

type -

in the

 

 

than RW, T, C and D. (Error down)

 

block No.

block

 

S064

The register designated by index modification

 

 

 

 

 

has exceeded the allowable range. That is,

 

 

 

 

 

out of RW, T, C and D.

 

 

 

 

 

(No error down)

 

 

 

 

 

Check the value of the index register.

Clock-calendar error

 

 

 

S00A

The data of built-in calendar LSI is illegal.

 

 

 

 

 

(No error down)

 

 

 

 

 

Set the date and time. (T1S only)

Duplicate entry No.

Program

Address

Entry No.

 

Multiple SUBR instructions which have the

 

type -

in the

 

 

same subroutine number are programmed.

 

block No.

block

 

 

(Error down)

 

 

 

 

 

Check the program.

EEPROM BCC error

Illegal

 

 

S004

BCC error has been detected in the user

 

BCC

 

 

S013

program of the EEPROM. (Error down)

 

 

 

 

 

Reload the program and execute EEPROM

 

 

 

 

 

write operation again.

EEPROM warning

Number

 

 

S007

The number of times of writing into EEPROM

 

of excess

 

 

 

has exceeded the life (100,000 times). (No

 

writing

 

 

 

error down)

 

 

 

 

 

Replace the unit because the data reliability

 

 

 

 

 

of the EEPROM will decrease.

I/O bus error

Unit No.

Data

 

S005

An abnormality has been detected in I/O bus

 

 

 

 

S020

checking. (Error down)

 

 

 

 

 

Check the expansion cable connection and

 

 

 

 

 

I/O module mounting status.

I/O mismatch

Unit No. -

Register

 

S005

The I/O allocation information and the actual

 

slot No.

No.

 

S021

I/O configuration are not identical.

 

 

 

 

 

(Error down)

 

 

 

 

 

Check the I/O allocation and the option card

 

 

 

 

 

mounting status.

I/O no answer

Unit No. -

Register

 

S005

No response from the T2 I/O module has

 

slot No.

No.

 

S022

been received. (Error down)

 

 

 

 

 

Check the I/O allocation, the expansion cable

 

 

 

 

 

connection and the T2 I/O module mounting

 

 

 

 

 

status.

I/O parity error

Unit No. -

Register

 

S005

I/O bus parity error has been detected in data

 

slot No.

No.

 

S023

read/write for T2 I/O modules. (Error down)

 

 

 

 

 

Check the expansion cable connection and

 

 

 

 

 

the T2 I/O module mounting status.

Illegal I/O reg

Unit No. -

Register

 

S005

The allocated I/O register address exceeds

 

slot No.

No.

 

S021

the limit, 32 words. (Error down)

 

 

 

 

 

Check the I/O allocation.

Basic Hardware and Function 301