6F3B0250
Basic Hardware and Function 189
7. Instructions
9 devices starting with R200 (R200 to R208) is specified as a shift register.
When R010 is OFF, the data of the shift r egister is reset to 0. (R200 to R208 are r eset to OFF)
The carr y f lag (CF = S050) is also reset t o O FF.
While R010 is O N t he following operation is enabled.
· When X 00A is O N ( shift left ) , the data of the shift reg ist er is shifted 1 bit to the upper address
direction w hen X009 is changed from OFF to ON. At the same time, the state of X008 is stored
in the leading bit ( R200) . The output (R012) indicates the state of the highest bit (R208).
· When X00A is OFF (shift right), the data of the shift register is shifted 1 bit to the lower address
direction w hen X009 is changed from OFF to ON. At the same time, the state of X008 is stored
in the highest bit (R208). The out put ( R012) indicat es the state of the lowest bit (R200).
The figure below shows an operation example.
(When X00A is ON and X009 is changed from O FF t o ON)
CF R208 R207 R206 R205 R204 R203 R202 R201 R200 X008
100110011 0
1 001100110
R012 is turned OFF
(When X00A is OFF and X009 is chang ed from OFF to ON)
X008 R208 R207 R206 R205 R204 R203 R202 R201 R200 CF
1 001100110
100110011 0
R012 is turned ON
Note
· When the shift input is O N, the shift oper ation is perfor m ed every scan. Use a transitional contact
for t he shift input t o det ect the state changing.
· For the data input, the shif t input and the enable input, dir ect linking to a connect ing point is not
allowed. In this case, insert a dummy contact (always ON special device = S04F, etc.) just before
the input. Refer to Not e of Shift register FUN 074.
Shift result
Shift result