7. Instructions

FUN 048

AND

AND

Expression

Input -[ A AND B ® C ]- Output

Function

When the input is ON, this instruction finds logical AND of A and B, and stores the result in C.

Execution condition

Input

 

Operation

Output

OFF

No execution

 

OFF

ON

Execution

 

ON

Operand

 

Name

 

 

Device

 

 

 

 

 

 

Register

 

 

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

I

J

K

 

 

A

Source

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

B

Source

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

C

AND

 

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

 

Ö

Example

When R012 is ON, logical AND operation is executed for the data of RW12 and the constant data HFF00, and the result is stored in D0030.

If the data of RW12 is H3456, the result H3400 is stored in D0030.

RW12

F E D C B A 9 8 7 6 5 4 3 2 1 0

0

0

 

1

1

0

1

 

0

0

0

1

0

1

0

1

1

0

 

3

 

 

 

4

 

 

 

5

 

 

 

6

 

 

 

 

 

 

 

 

 

 

 

AND

 

 

 

 

 

 

 

Constant

1 1 1 1 1 1 1 1 0 0 0 0 0 0 0 0

F F

0 0

D0030

0 0 1 1 0 1 0 0 0 0 0 0 0 0 0 0

3

4

0

0