8. Special I/O Functions

8.2 Variable input filter constant

Function

The input filter constant (ON/OFF delay time) of the leading 8 points X000 to X007 can be specified by user program within the range of 0 to 15 ms. The default is 10 ms. The setting value is recognized at the first scan. Therefore, it cannot be changed after the second scan.

Related registers

SW16 Function selection. Refer to section 8.1.

SW17 Input filter constant value

F E D C B A 9 8 7 6 5 4 3 2 1 0

No use (set to 0)

Setting value

0 to 15

Operation

Input signal

T

T

T

T

Internal logic

 

 

 

Scan cycle

 

 

 

X device

 

 

 

T: Input filter constant (0 to 15 ms)

Sample program

This program sets the input filter constant to 3 ms.

NOTE

For the AC input types, this function works as extended delay time.

On delay time = 25 ms + setting time

Off delay time = 30 ms + setting time

272 T1/T1S User’s Manual