6F3B0250

7. Instructions

FUN 180

ABS

Absolute value

Expression

Input -[ A ABS B ]- Output

Function

When the input is ON, this instruction finds the absolute value of operand A, and stores it in B.

Execution condition

Input

 

Operation

Output

OFF

No execution

 

OFF

ON

Execution

 

ON

Operand

 

Name

 

 

Device

 

 

 

 

 

 

Register

 

 

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

I

J

K

 

 

A

Source

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

 

B

Destination

 

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

 

 

Example

When X006 is ON, the absolute value of RW38 is stored in D0121.

For example, if RW38 is -12000, the absolute value 12000 is stored in D0121.

D0121

32767

12000

-32767

-12000

0

32767

RW38

Note

·The data range of A is -32768 to 32767. If the data of A is -32768, 32767 is stored in B.

Basic Hardware and Function 249