6F3B0250

7. Instructions

 

 

N

 

 

Negative pulse contact

 

 

 

 

 

 

 

 

 

 

 

 

Expression

A

Input N Output

T1S only

Function

When the input is ON and the device A is changed from ON to OFF (ON at last scan and OFF at this scan), the output is turned ON.

This instruction is used to detect the device changing from ON to OFF.

Execution condition

Input

Operation

Output

OFF

Regardless of the state of device A

OFF

ON

State of device A is OFF

A is OFF at last scan

OFF

 

 

A is ON at last scan

ON

 

State of device A is ON

 

OFF

Operand

 

Name

 

 

Device

 

 

 

 

 

 

Register

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

I

J

K

 

 

A

Device

Ö

Ö

Ö

Ö

Ö

Ö

 

 

 

 

 

 

 

 

 

 

 

 

Example

R100 comes ON for only 1 scan when X000 is ON and X003 changes to OFF.

X000

X003

R100

1 scan time 1 scan time

Note

·The maximum usable number in a program is 2048.

( P N (P) (N) total)

144 T1/T1S User’s Manual