6F3B0250

7. Instructions

FUN 144

STIZ

Step sequence initialize

Expression

Input -[ STIZ (n) A ]- Output

Function

When the input is ON, n devices starting with A are reset to OFF, and A is set to ON.

This instruction is used to initialize a series of step sequence. The step sequence is useful to describe a sequential operation.

Execution condition

Input

Operation

Output

OFF

No execution

OFF

ON

Execution at the rising edge of the input

ON

Operand

 

Name

 

 

Device

 

 

 

 

 

 

Register

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

I

J

K

 

 

n

Size of step

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 - 64

 

 

sequence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

Start device

 

 

Ö

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example

When R020 is changed from OFF to ON, R400 is set to ON and subsequent 9 devices (R401 to R409) are reset to OFF.

This instruction initializes a series of step sequence, 10 devices starting with R400.

R409

R408

R407

R406

R405

R404

R403

R402

R401

R400

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

OFF

ON

10 devices starting with R400

Note

·The STIZ instruction is used together with STIN (FUN 145) and STOT (FUN 146) instructions to configure the step sequence.

·The STIZ instruction is executed only when the input is changed from OFF to ON.