6F3B0250

7. Instructions

FUN 114

SET

Device/register set

Expression

Input -[ SET A ]- Output

Function

When the input is ON, the device A is set to ON if A is a device, or the data HFFFF is stored in the register A if A is a register.

Execution condition

Input

 

Operation

Output

OFF

No execution

 

OFF

ON

Execution

 

ON

Operand

 

Name

 

 

Device

 

 

 

 

 

 

Register

 

 

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

I

J

K

 

 

A

Device or

 

Ö

Ö

Ö

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

 

 

 

register

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example 1 (device set)

When R010 is ON, R025 is set to ON. The state of R025 is remained even if R010 comes OFF.

Example 2 (register set)

When R010 is ON, the data HFFFF is stored in RW20. (R200 to R20F are set to ON) The state of RW20 is remained even if R010 comes OFF.

214 T1/T1S User’s Manual

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Page 216
Image 216
Toshiba PROSEC T1 T1S, 6F3B0250 user manual Set, Device/register set, Example 1 device set, Example 2 register set