10. Troubleshooting

Error message and related information

Special

Meaning and countermeasures

Event

Info 1

Info 2

Info 3

device

 

Sys RAM check err

Error

Error data

Test data

S004

In the power-up initialization, an error has

 

address

 

 

S011

detected by system RAM read/write

 

 

 

 

 

checking. (Error down and programming tool

 

 

 

 

 

cannot be connected)

 

 

 

 

 

Replace the unit if the error remains after

 

 

 

 

 

power OFF and ON again.

Sys ROM BCC error

Illegal

 

 

S004

BCC error has been detected in the system

 

BCC

 

 

S010

program in the ROM. (Error down and

 

 

 

 

 

programming tool cannot be connected)

 

 

 

 

 

Replace the unit if the error remains after

 

 

 

 

 

power OFF and ON again.

System power off

 

 

 

 

Power OFF (no error)

System power on

 

 

 

 

Power ON (no error)

Sub-r nesting err

Program

Address

Sub-r No.

 

T1:

 

type -

in the

 

 

CALL instruction is programmed in a

 

block No.

block

 

 

subroutine program. (Error down)

 

 

 

 

 

Correct the program.

 

 

 

 

 

T1S:

 

 

 

 

 

The nesting of subroutines exceeds 3 levels.

 

 

 

 

 

(Error down)

 

 

 

 

 

Correct the program.

WD timer error

Address 1

Address 2

 

S004

The watchdog timer error has occurred.

 

 

 

 

S01F

(Error down)

 

 

 

 

 

If the error occurs frequently, replace the unit.