10. Troubleshooting
Error message and related information | Special | Meaning and countermeasures | |||
Event | Info 1 | Info 2 | Info 3 | device |
|
Sys RAM check err | Error | Error data | Test data | S004 | In the |
| address |
|
| S011 | detected by system RAM read/write |
|
|
|
|
| checking. (Error down and programming tool |
|
|
|
|
| cannot be connected) |
|
|
|
|
| Replace the unit if the error remains after |
|
|
|
|
| power OFF and ON again. |
Sys ROM BCC error | Illegal |
|
| S004 | BCC error has been detected in the system |
| BCC |
|
| S010 | program in the ROM. (Error down and |
|
|
|
|
| programming tool cannot be connected) |
|
|
|
|
| Replace the unit if the error remains after |
|
|
|
|
| power OFF and ON again. |
System power off |
|
|
|
| Power OFF (no error) |
System power on |
|
|
|
| Power ON (no error) |
Program | Address |
| T1: | ||
| type - | in the |
|
| CALL instruction is programmed in a |
| block No. | block |
|
| subroutine program. (Error down) |
|
|
|
|
| Correct the program. |
|
|
|
|
| T1S: |
|
|
|
|
| The nesting of subroutines exceeds 3 levels. |
|
|
|
|
| (Error down) |
|
|
|
|
| Correct the program. |
WD timer error | Address 1 | Address 2 |
| S004 | The watchdog timer error has occurred. |
|
|
|
| S01F | (Error down) |
|
|
|
|
| If the error occurs frequently, replace the unit. |
304 T1/T1S User’s Manual
CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net