6F3B0250

6. Programming Information

6.5 T1S memory mode setting

The program capacity of the T1S is 8 k steps. However, user can set the T1S’s program capacity to 4 k steps. It is called the T1S’s memory mode.

That is, the T1S has two memory modes, 8 k mode and 4 k mode.

In the 4 k mode, on-line program changes become available, although the program capacity is limited to 4 k steps. Refer to section 6.9 for the on-line debug support functions.

To set the T1S’s memory mode, write 4 k or 8 k on the Program Size Setting of the System Parameters using the programming tool. Then execute the EEPROM write command.

NOTE

There is no memory mode setting for the standard T1. The program capacity of the standard T1 is 2 k steps fixed.

Basic Hardware and Function 109

CTi Automation - Phone: 800.894.0412 - Fax: 208.368.0415 - Web: www.ctiautomation.net - Email: info@ctiautomation.net

Page 111
Image 111
Toshiba 6F3B0250, PROSEC T1 T1S user manual T1S memory mode setting