6F3B0250

7. Instructions

FUN 108

U>

Unsigned greater than

T1S only

Expression

Input -[ A U> B ]- Output

Function

When the input is ON, the data of A and the data of B are compared, and if A is greater than B, the output is turned ON.

Execution condition

Input

 

 

Operation

Output

OFF

No execution

 

 

OFF

ON

Execution

A > B

 

ON

 

 

A £ B

 

OFF

Operand

 

Name

 

 

Device

 

 

 

 

 

 

Register

 

 

 

 

Constant

Index

 

 

X

Y

R

S

T.

C.

XW

YW

RW

SW

T

C

D

I

J

K

 

 

A

Compared

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

 

data

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

B

Reference data

 

 

 

 

 

 

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Ö

Example

When R00C is ON, the data of D0125 is compared with the constant data 40000, and if the data of D0125 is greater than 40000, R020 is turned ON.

If the data of D0125 is 52000, the comparison result is true. Consequently, R020 is turned ON.

D0125

52000

>Constant

40000

R020 is ON

If the data of D0125 is 21000, the comparison result is false. Consequently, R020 is turned OFF.

D0125

21000

£Constant

40000

R020 is OFF

Note

·This instruction deals with the data as unsigned integer (0 to 65535).