10. Troubleshooting
10.1.1Power supply check
If the PWR (power) LED is not lit after power on, check the following points.
Check the power connection
Correct
Check the power voltage at the T1/T1S’s terminal
Normal
Remove the programmer
port connector
Still unlit
Remove the 24 Vdc service power terminals if it is used
Still unlit
Remove the option cards and
the expansion cable
Lit
Confirm the internal 5 Vdc
current consumption if
option card, expansion rack or expansion unit is used
Within the limit
Insert the removed option cards one by one to pinpoint the faulty card
Normal
Connect the expansion rack or unit again. For expansion rack, insert the I/O modules one by one to pinpoint the faulty module
Connection terminals are correct. The terminal screws are not loose. The terminal block is installed securely.
85 to 132/170 to 264 Vac (50/60 Hz) or 20.4 to 28.8 Vdc (DC power)
If the PWR LED becomes normal, the internal 5 Vdc can be shorted in the external connections of this port.
If the PWR LED becomes normal, the 24 Vdc service power can be over load.
If the PWR LED is still unlit, the T1/T1S basic unit may be faulty. Replace the unit.
The 5 Vdc capacity for option cards and expansion rack/unit is 1 A.
(If the HP911A is connected, it requires
0.2A, and if
Replace the faulty option card.
Replace the faulty I/O module or faulty expansion rack/unit.
Basic Hardware and Function 295