6F3B0250
Basic Hardware and Function 143
7. Instructions
PPositive pulse contact
Expression
A
Input P Output
Function
When the input is ON and the device
A
is changed from OFF to ON (OFF at last scan and ON at this
scan), the out put is turned ON.
This instr uct ion is used to detect the device changing from O FF to ON.
Execution condition
Input Operation Output
OFF Regardless of the state of device
A
OFF
ON State of device
A
is OFF OFF
State of device
A
is ON
A
is OFF at last scan ON
A
is ON at last scan OFF
Operand
Name Device Re
g
ister Constant Index
X Y R S T. C. XW YW RW SW T C D I J K
A
Device ÖÖÖÖÖÖ
Example
R100 comes ON f or only 1 scan when X000 is ON and X 003 changes to ON.
X000
X003
R100
1 scan time 1 scan time
Note
· The maximum usable num ber in a pr ogram is 2048.
(P N (P) (N) total)
T1S only