Fan modules

7.1.4Replacing the defective fan module

Figure 50: Identifying and removing a defective fan module

ÊIdentify the defective fan module. The indicator of the defective fan lights up Orange, see circle in figure 50.

ÊHave the new fan module ready for the installation.

VCAUTION!

Never leave the fan module bay empty for more than two minutes during operation. Otherwise, excessive temperatures could damage system components.

ÊPress the handle (1) and lift the fan module out of the housing (2).

ÊInsert the new fan module in the empty bay until it engages.

The new fan module is tested by Server Management. The indicator then either does not light at all (fan is OK) or lights up in Orange (fan is not OK).