Cables
15.5.2 Starting the task
ÊPerform the following procedures:
1."Opening the rack door" on page 40
2."Locate the faulty server" on page 37
3."Shutting down the server" on page 41
4."Sliding the server out of the rack" on page 42
5."Opening the server" on page 44
6.Remove all PSUs, see "Removing the power supply unit" on page 58
7.Remove all CPUMEMRs, see "Removing the CPUMEMR" on page 190
IBefore removing the CPUMEMRs, take a note on the installation slot number for each CPUMEMR. Make sure that you reinstall the CPUMEMR in the slot it was located before the replacement.
8.Remove all expansion cards and dummy modules in PCIe slots #8 to #17, see "Expansion cards and BBU" on page 105
IBefore removing the expansion cards, take a note on the installation slot number for each card. Make sure that you reinstall the card in the slot it was located before the replacement.
9.Remove the PCI Riser, see "Expansion cards and BBU" on page 105
10.Remove the BBU holder, see "Expansion cards and BBU" on page 105
334 | Maintenance Manual | RX900 S1 |