4. SIGNALS AND WIRING
4.3 Explanation of power supply system 4.3.1 Signal explanations POINT For the layout of connector and terminal block, refer to outline drawings in chapter 12.
Abbreviation Connection target
(Application) Description
Supply the following power to L1, L2, L3. For the 1-phase 200V to 230VAC power supply, connect
the power supply to L1, L2, and keep L3 open.
Servo amplifier
Power supply
MR-J3-
10T to
70T
MR-J3-
100T to
22KT
MR-J3-
10T1 to
40T1
3-phase 200V to 230VAC, 50/60Hz L1L2L3
1-phase 200V to 230VAC, 50/60Hz L1L2
1-phase 100V to 120VAC, 50/60Hz L1L2
Servo amplifier
Power supply
MR-J3-
60T4 to
22KT4
3-phase 380V to 480VAC, 50/60Hz L1L2L3
L1
L2
L3
Main circuit power
supply
P1
P2
Power factor
improving DC
reactor
1) MR-J3-700T(4) or less
When not using the power factor improving DC reactor, connect P1 and P2. (Factory-wired.)
When using the power factor improving DC reactor, disconnect P1 and P2, and connect the
power factor improving DC reactor to P1 and P2.
2) MR-J3-11KT(4) to 22KT(4)
MR-J3-11KT(4) to 22KT(4) do not have P2.
When not using the power factor improving reactor, connect P1 and P. (Factory-wired)
When using the power factor improving reactor, connect it to P1 and P.
Refer to section 14.11.
P
C
D
Regenerative
option
1) MR-J3-350T or less MR-J3-200T4 or l ess
When using servo amplifier built-in regenerative resistor, connect P( ) and D. (Factory-wired)
When using regenerative option, disconnect P( ) and D, and connect regenerative option to
P and C.
2) MR-J3-350T4 500T(4) 700T(4)
MR-J3-350T4 500T(4) and 700T(4) do not have D.
When using servo amplifier built-in regenerative resistor, connect P and C. (Factory-wired)
When using regenerative option, disconnect P and C, and connect regenerative option to P
and C.
3) MR-J3-11KT(4) to 22KT(4)
MR-J3-11KT(4) to 22KT(4) do not have D.
When not using the power regenerative converter and the brake unit, make sure to connect
the regenerative option to P and C.
Refer to section 14.2 to 14.5.
Supply the following power to L11 L21.
Servo amplifier
Power supply
MR-J3-
10T to
22KT
MR-J3-
10T1 to
40T1
MR-J3-
60T4 to
22KT4
1-phase 200V to 230VAC, 50/60Hz L11 L21
1-phase 100V to 120VAC, 50/60Hz L11 L21
1-phase 380V to 480VAC, 50/60Hz L11 L21
L11
L21
Control circuit
power supply
U
V
W
Servo motor power Connect to the servo motor power supply terminals (U, V, W). During power-on, do not open or
close the motor power line. Otherwise, a malfunction or faulty may occur.
N
Regenerative
converter
Brake unit
When using the power regenerative converter/brake unit, connect it to P and N.
Do not connect to servo amplifier MR-J3-350T(4) or less.
For details, refer to section 14.3 to 14.5.
Protective earth
(PE)
Connect to the earth terminal of the servo motor and to the protective earth (PE) of the control
box to perform grounding.