14 - 24
14. OPTIONS AND AUXILIARY EQUIPMENT
(b) MR-J3-350T4 MR-J3-500T(4) MR-J3-700T(4)
Always remove the wiring (across P-C) of the s ervo amplifier built-in regenerative resistor a nd fit the
regenerative option across P-C.
The G3 and G4 terminals act as a thermal sens or. G3-G4 is opened when the regenerative o ption
overheats abnormally.
PP
C
G3
(Note 2)
5m or less
G4
C
Servo amplifier
Always remove wiring (across P-C) of servo
amplifier built-in regenerative resistor.
Regenerative option
Cooling fan (Note 1)
Note 1. When using the MR-RB51, MR-RB3G-4, MR-RB5G-4, MR-RB34-4 or MR-RB54-4,
forcibly cool it with a cooling fan (92 92, minimum air flow : 1.0m3).
2. Make up a sequence which will switch off the magnetic contactor (MC) when abnormal
heating occurs.
G3-G4 contact specifications
Maximum voltage: 120V AC/DC
Maximum current: 0.5A/4.8VDC
Maximum capacity: 2.4VA
When using the regenerative resistor optio n, remove the servo amplifier's built-in rege nerative resistor
terminals (across P-C), fit them back to back , and secure them to the frame with the accessory scr ew as
shown below.
Mounting method
Accessory screw