15 - 36
15. COMMUNICATION FUNCTION
(5) Output signal pin ON/OFF output signal (DO) for ced output
In the test operation mode, the output signal p ins can be turned on/off independently of the serv o status.
Using command [9][0], disable the output signals in advance.
(a) Choosing DO forced output in test operation m ode
Transmit command [8][B] data No. [0][0] data "0004" to choose DO forced output.
00
Selection of test operation mode
4: DO forced output (output signal forced output)
04
(b) External output signal ON/OFF
Transmit the following communication commands .
Command Data No. Setting data
[9][2] [A][0] See below.
Command of each bit is sent to the slave station in hexadecimal.
b31 b0
0: OFF
1: ON
b1
bit CN6 connector pin bit CN6 connector pin bit CN6 connector pin bit CN6 connector pin
0 14 8 16 24
1 15 9 17 25
2 16 10 18 26
3 11 19 27
4 12 20 28
5 13 21 29
6 14 22 30
7
15
23
31
(c) Canceling DO forced output
Transmit command [8][B] + data No. [0][0] + data to cancel DO forced output.
Command Data No. Transmission data Description
[8][B] [0][0] 0000 Cancel DO forced output
(6) Motorless operation
(a) Performing motorless operation
Transmit command [8][B] + data No. [0][0] + d ata "0003" to perform motorless operation.
Selection of test operation mode
3: Motorless operation
0003
To perform operation after performing the motorl ess operation, issue a command from the host
controller.
(b) Canceling motorless operation
The motorless operation cannot be canceled in the sam e way as the test operation mode (transmit
command [8][B] + data No. [0][0] + data "0000"). To cancel t he motorless operation, power on the servo
amplifier and shift to the CC-Link operation m ode beforehand.