3 - 34
3. CC-LINK COMMUNICATION FUNCTIONS
3.6 Data communication timing charts
3.6.1 Monitor codes
(1) When 1 station is occupied
Data HOLD
ON
OFF
Monitor 1
(RWwn)
Monitor 2
(RWwn+1)
Monitor execution
demand (RYn8)
ON
OFF
Monitoring
(RXn8)
Monitor 1 data
(RWrn)
Monitor 2 data
(RWrn+1)
Respond code
(RWrn+2)
Set the monitor codes (refer to section 3.5.3) to Monitor 1 (RWwn) and Monitor 2 (RWwn+1) and turn Mo nitor
output execution demand (RYn8) to ON. Turning Moni tor execution demand (RYn8) to ON sets the next data.
Data are all hexadecimal numbers. At this tim e, Monitoring (RXn8) turns to ON at the same t ime.
Monitor data 1 (RWrn): Data demanded by Monitor 1 (RWwn)
Monitor data 2 (RWrn+1): Data demanded by Monit or 2 (RWwn+1)
For 32-bit data, set the lower 16 bits of the monit or code to Monitor 1 (RWwn) and the upper 16 bits to Monitor
2 (RWwn+1) and read them simultaneously.
The monitor data set to the remote register are always updated while Monitor execution demand (RYn8) is ON.
When Monitoring (RXn8) turns to OFF, the data set to Mon itor data RWrn, RWrn+1 are held. If the monitor
code not in the specifications is set to either Mo nitor 1 (RWwn) or Monitor 2 (RWwn+1), the corresponding
error code ( 1) is set to respond code.