Chapter 14 | Product Specifications |
The following sections detail the input, output, environmental, and battery specifications for the UPS.
14.1Model Numbers
The UPS systems are housed in free‐standing, double‐front cabinets with safety shields behind the doors. The UPS systems are available in 50/60 Hz with various output power ratings. Smaller models within a system may be upgraded in the field to larger models:
System | Models | Notes |
|
|
|
Powerware 9315‐625 | 562, 500, 450, 400 kW | 50/60 Hz |
|
|
|
Powerware 9315‐750 | 675, 600, 562, 500 kW | 60 Hz only |
|
|
|
14.2UPS System Input
Operating Input Voltage | 600 Vac for operation from 510 Vac to 660 Vac (60 Hz only) |
(Nominal | 480 Vac for operation from 408 Vac to 528 Vac (60 Hz only) |
| 400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only) |
|
|
Operating Input Frequency | "3 Hz of nominal (50 Hz or 60 Hz) |
Range |
|
|
|
Operating Input Current | Battery Charge |
| 125% of full load for overload + battery charge |
| Actual load + 25% of full load for battery charge with 0.8 pF |
| output units |
| 115% of full load for overload + battery charge |
| Actual load + 15% of full load for battery charge with 0.9 pF |
| output units |
| Reduced for Generator |
| Adjustable, set to 102% |
|
|
Input Current Harmonic | 5% THD at full load (with input filter option installed) |
Content |
|
|
|
Power Walk‐In | Adjustable |
|
|
Power Factor | Minimum 0.85 |
|
|
Line Surges | 6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801‐4 |
|
|
EATON Powerware® 9315 UPS |