Chapter 14

Product Specifications

The following sections detail the input, output, environmental, and battery specifications for the UPS.

14.1Model Numbers

The UPS systems are housed in free‐standing, double‐front cabinets with safety shields behind the doors. The UPS systems are available in 50/60 Hz with various output power ratings. Smaller models within a system may be upgraded in the field to larger models:

System

Models

Notes

 

 

 

Powerware 9315‐625

562, 500, 450, 400 kW

50/60 Hz

 

 

 

Powerware 9315‐750

675, 600, 562, 500 kW

60 Hz only

 

 

 

14.2UPS System Input

Operating Input Voltage

600 Vac for operation from 510 Vac to 660 Vac (60 Hz only)

(Nominal +10/–15%)

480 Vac for operation from 408 Vac to 528 Vac (60 Hz only)

 

400 Vac for operation from 340 Vac to 440 Vac (50/60 Hz only)

 

 

Operating Input Frequency

"3 Hz of nominal (50 Hz or 60 Hz)

Range

 

 

 

Operating Input Current

Battery Charge

 

125% of full load for overload + battery charge

 

Actual load + 25% of full load for battery charge with 0.8 pF

 

output units

 

115% of full load for overload + battery charge

 

Actual load + 15% of full load for battery charge with 0.9 pF

 

output units

 

Reduced for Generator

 

Adjustable, set to 102%

 

 

Input Current Harmonic

5% THD at full load (with input filter option installed)

Content

 

 

 

Power Walk‐In

Adjustable 3–60 second rectifier ramp‐up to full utility load

 

 

Power Factor

Minimum 0.85

 

 

Line Surges

6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801‐4

 

 

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com

14-1