INSTALLATION REFERENCE
14.External overcurrent protection is not provided by this product, but is required by codes. See Table E through Table G starting on page
15.Table K lists the maximum rating for continuous duty rated input circuit breakers.
C A U T I O N
To reduce the risk of fire, connect only to a circuit provided with maximum input circuit breaker current ratings from Table K according to the NEC, ANSI/NFPA 70.
Table K. Maximum Input Circuit Breaker Ratings
|
| Input Voltage Rating |
| |
UPS Model |
|
|
| |
400V | 480V | 600V | ||
| ||||
|
|
|
| |
1000A | N/A | N/A | ||
|
|
| ||
|
|
|
| |
1200A | N/A | N/A | ||
|
|
| ||
|
|
|
| |
N/A | 1000A | 800A | ||
|
|
| ||
|
|
|
| |
N/A | 1200A | 1000A | ||
|
|
| ||
|
|
|
|
16.Source protection for the AC input should be treated as if you were supplying a 750 kVA
17.The input breaker (CB1) has a trip rating of 1200 amps AT and a standard ampere interrupting capacity (AIC) of 65,000 in symmetrical RMS amps. An optional 100,000 AIC breaker is available.
18.The input and bypass
19.The line‐to‐line unbalanced output capability of the UPS is limited only by the full load per phase current values for AC output to critical load shown in Table E through Table G. The recommended line‐to‐line load unbalance is 50% or less.
20.Output overcurrent protection and output disconnect switch are to be provided by the user. Table L lists the maximum rating for continuous duty rated output circuit breakers satisfying the criteria for both.
EATON Powerware® 9315 UPS |