Powerware Powerware 9315 Table N lists the battery shunt trip trip wiring requirements

Models: Powerware 9315

1 154
Download 154 pages 18.66 Kb
Page 130
Image 130

INSTALLATION REFERENCE

Table L. Maximum Output Circuit Breaker Ratings

 

 

Output Voltage Rating

 

UPS Model

 

 

 

400V

480V

600V

 

 

 

 

 

PW9315-625/400

800A

N/A

N/A

PW9315-625/450

 

 

 

 

 

 

 

PW9315-625/500

1000A

N/A

N/A

PW9315-625/562

 

 

 

 

 

 

 

PW9315-750/500

N/A

800A

700A

PW9315-750/562

 

 

 

 

 

 

 

PW9315-750/600

N/A

1000A

800A

PW9315-750/675

 

 

 

 

 

 

 

21.DC input overcurrent protection and disconnect switch are to be provided by the user. Table M lists the maximum rating for continuous duty rated circuit breakers satisfying the criteria for both.

Table M. Maximum DC Input Circuit Breaker Ratings

 

 

Output Voltage Rating

 

UPS Model

 

 

 

400V

480V

600V

 

 

 

 

 

PW9315-625/400

1600A

N/A

N/A

PW9315-625/450

 

 

 

 

 

 

 

PW9315-625/500

1800A

N/A

N/A

PW9315-625/562

2000A

 

 

 

 

 

 

PW9315-750/500

N/A

1800A

1800A

PW9315-750/562

2000A

2000A

 

 

 

 

 

PW9315-750/600

N/A

2000A

2000A

PW9315-750/675

2300A

2300A

 

 

 

 

 

22.Table N lists the battery shunt trip trip wiring requirements.

Table N. Battery Shunt Trip Wiring Requirements

Description

ST

 

 

CB2TB Points

9, 10

 

 

Output Max Pulse

220 VA instantaneous

 

 

Wiring

#18 AWG minimum

 

 

23.There is no DC disconnect device within the UPS.

24.The DC input to the UPS is protected by internal fuses F30 and F31.

25.Recommended wire size is #18–14 AWG.

26.Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at 2 volts per cell.

27.The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current.

A-20

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com