INSTALLATION REFERENCE
Table L. Maximum Output Circuit Breaker Ratings
|
| Output Voltage Rating |
| |
UPS Model |
|
|
| |
400V | 480V | 600V | ||
| ||||
|
|
|
| |
800A | N/A | N/A | ||
|
|
| ||
|
|
|
| |
1000A | N/A | N/A | ||
|
|
| ||
|
|
|
| |
N/A | 800A | 700A | ||
|
|
| ||
|
|
|
| |
N/A | 1000A | 800A | ||
|
|
| ||
|
|
|
|
21.DC input overcurrent protection and disconnect switch are to be provided by the user. Table M lists the maximum rating for continuous duty rated circuit breakers satisfying the criteria for both.
Table M. Maximum DC Input Circuit Breaker Ratings
|
| Output Voltage Rating |
| |
UPS Model |
|
|
| |
400V | 480V | 600V | ||
| ||||
|
|
|
| |
1600A | N/A | N/A | ||
|
|
| ||
|
|
|
| |
1800A | N/A | N/A | ||
2000A | ||||
|
| |||
|
|
|
| |
N/A | 1800A | 1800A | ||
2000A | 2000A | |||
| ||||
|
|
|
| |
N/A | 2000A | 2000A | ||
2300A | 2300A | |||
| ||||
|
|
|
|
22.Table N lists the battery shunt trip trip wiring requirements.
Table N. Battery Shunt Trip Wiring Requirements
Description | ST |
|
|
CB2TB Points | 9, 10 |
|
|
Output Max Pulse | 220 VA instantaneous |
|
|
Wiring | #18 AWG minimum |
|
|
23.There is no DC disconnect device within the UPS.
24.The DC input to the UPS is protected by internal fuses F30 and F31.
25.Recommended wire size is
26.Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current is computed at 2 volts per cell.
27.The battery wiring used between the battery and the UPS should not allow a voltage drop of more than 1% of nominal DC voltage at rated battery current.
EATON Powerware® 9315 UPS |