INSTALLATION REFERENCE
10.Per NEC, Article 300‐20(a), all
11.Conduit is sized to accommodate one neutral conductor the same size as the phase conductor (if applicable) and one 2/0 ground conductor.
12.Conduit sizes were chosen from NEC Table C1, type letters RHH, RHW, RHW‐2, TW, THW, THHW, THW‐2.
Table I. Power Cable Conduit Requirements
UPS Model | Voltage | Terminal | Number of Wires | Minimum Conduit | Number of | |
in Conduit | Trade Size | Conduits | ||||
|
|
| ||||
|
|
|
|
|
| |
|
| AC Input to UPS (A, B, C, Ground) | 5 | 3.5” | 3 | |
|
|
|
|
|
| |
600 | AC Input to MBC (A, B, C, Ground) | 4 | 3” | 3 | ||
|
|
|
|
| ||
| Output (A, B, C, Neutral, Ground) | 4 | 3” | 3 | ||
| ||||||
|
|
|
|
| ||
| 384 | Battery | 4 | 4” | 3 | |
| (Positive, Negative, Ground) | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
|
| AC Input to UPS (A, B, C, Ground) | 5 | 4” | 3 | |
|
|
|
|
|
| |
480 | AC Input to MBC (A, B, C, Ground) | 6 | 3.5” | 3 | ||
|
|
|
|
| ||
| Output (A, B, C, Neutral, Ground) | 6 | 3.5” | 3 | ||
| ||||||
|
|
|
|
| ||
| 384 | Battery | 4 | 4” | 3 | |
| (Positive, Negative, Ground) | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
|
| AC Input to UPS (A, B, C, Ground) | 5 | 3” | 3 | |
|
|
|
|
|
| |
600 | AC Input to MBC (A, B, C, Ground) | 5 | 3” | 3 | ||
|
|
|
|
| ||
| Output (A, B, C, Neutral, Ground) | 5 | 3” | 3 | ||
| ||||||
|
|
|
|
| ||
| 384 | Battery | 4 | 3.5” | 3 | |
| (Positive, Negative, Ground) | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
|
| AC Input to UPS (A, B, C, Ground) | 5 | 3.5” | 3 | |
|
|
|
|
|
| |
480 | AC Input to MBC (A, B, C, Ground) | 4 | 3” | 3 | ||
|
|
|
|
| ||
| Output (A, B, C, Neutral, Ground) | 4 | 3” | 3 | ||
| ||||||
|
|
|
|
| ||
| 384 | Battery | 4 | 3.5” | 3 | |
| (Positive, Negative, Ground) | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
|
| AC Input to UPS (A, B, C, Ground) | 4 | 3.5” | 4 | |
|
|
|
|
|
| |
400 | AC Input to MBC (A, B, C, Ground) | 5 | 3.5” | 3 | ||
|
|
|
|
| ||
| Output (A, B, C, Neutral, Ground) | 5 | 3.5” | 3 | ||
| ||||||
|
|
|
|
| ||
| 384 | Battery | 5 | 4” | 2 | |
| (Positive, Negative, Ground) | |||||
|
|
|
|
| ||
|
|
|
|
|
| |
|
| AC Input to UPS (A, B, C, Ground) | 5 | 3” | 3 | |
|
|
|
|
|
| |
400 | AC Input to MBC (A, B, C, Ground) | 5 | 3” | 3 | ||
|
|
|
|
| ||
| Output (A, B, C, Neutral, Ground) | 5 | 3” | 3 | ||
| ||||||
|
|
|
|
| ||
| 384 | Battery | 5 | 3.5” | 2 | |
| (Positive, Negative, Ground) | |||||
|
|
|
|
| ||
|
|
|
|
|
|
EATON Powerware® 9315 UPS |