USING FEATURES AND OPTIONS

10.4Optional Relay Interface Module

The optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the Parallel Capacity/Redundant system. Figure 10‐2 shows the RIM with its four 15‐pin connectors labeled J1 through J4.

 

 

Figure 10‐2. RIM

The RIM can provide the following signals:

 

 

 

UPS AVAILABLE

Pins 1 and 12

Contacts are closed when the UPS is operating in Normal

 

 

mode or ready to supply the load.

 

 

 

UPS OFF LINE

Pins 3 and 13

Contacts are open when the UPS is offline. Contacts are

 

 

closed when the UPS is poerating Normal mode.

 

 

 

BATTERY WEAK

Pins 5 and 14

Contacts are closed when approximately two minutes of

 

 

battery time is remaining, before the critical load is lost.

 

 

 

UTILITY FAILURE

Pins 6 and 15

Contacts are closed when Utility Failure is detected.

 

 

 

10-4

EATON Powerware® 9315 UPS (500–750 kVA) Installation and Operation Manual S 164201244 Rev E www.powerware.com

Page 82
Image 82
Powerware Powerware 9315 operation manual Optional Relay Interface Module, ‐2. RIM