10.4Optional Relay Interface Module

USING FEATURES AND OPTIONS

10.4Optional Relay Interface Module

The optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the Parallel Capacity/Redundant system. Figure 10‐2 shows the RIM with its four 15‐pin connectors labeled J1 through J4.

 

 

Figure 10‐2. RIM

The RIM can provide the following signals:

 

 

 

UPS AVAILABLE

Pins 1 and 12

Contacts are closed when the UPS is operating in Normal

 

 

mode or ready to supply the load.

 

 

 

UPS OFF LINE

Pins 3 and 13

Contacts are open when the UPS is offline. Contacts are

 

 

closed when the UPS is poerating Normal mode.

 

 

 

BATTERY WEAK

Pins 5 and 14

Contacts are closed when approximately two minutes of

 

 

battery time is remaining, before the critical load is lost.

 

 

 

UTILITY FAILURE

Pins 6 and 15

Contacts are closed when Utility Failure is detected.

 

 

 