USING FEATURES AND OPTIONS
10.4Optional Relay Interface Module
The optional Relay Interface Module (RIM) uses relay contact closures to indicate the operating status and alarm condition of the Parallel Capacity/Redundant system. Figure 10‐2 shows the RIM with its four 15‐pin connectors labeled J1 through J4.
|
| Figure 10‐2. RIM |
The RIM can provide the following signals: | ||
|
|
|
UPS AVAILABLE | Pins 1 and 12 | Contacts are closed when the UPS is operating in Normal |
|
| mode or ready to supply the load. |
|
|
|
UPS OFF LINE | Pins 3 and 13 | Contacts are open when the UPS is offline. Contacts are |
|
| closed when the UPS is poerating Normal mode. |
|
|
|
BATTERY WEAK | Pins 5 and 14 | Contacts are closed when approximately two minutes of |
|
| battery time is remaining, before the critical load is lost. |
|
|
|
UTILITY FAILURE | Pins 6 and 15 | Contacts are closed when Utility Failure is detected. |
|
|
|
EATON Powerware® 9315 UPS |