COMMUNICATION
If you select 1, 2, or 3 from this menu, the following menu is displayed:
Enable/Disable (Function)
Enabled Building Alarm Number(s) 1 4
Enter E# to Enable Building Alarm Number #
Enter D# to Disable Building Alarm Number #
Enter <CR> for No Change
Enter Selection:
Where (Function) indicates the function the building alarm is being programmed for. The text following the “Enabled Building Alarm Number(s)” label indicates which building alarms are currently enabled for the function. In this example, Building Alarms 1 and 4 are enabled. A building alarm can only be programmed for one special function at a time from these menus. Enabling a building alarm for a special function automatically enables the alarm. If you disable a special function, the building alarm is also disabled.
If you select entry 4 from this menu, the following menu is displayed:
Enable/Disable Building Alarm
Enabled Building Alarm Number(s) 1 4
Enter E# to Enable Building Alarm Number #
Enter D# to Disable Building Alarm Number #
Enter <CR> for No Change
Enter Selection:
The text following the “Enabled Building Alarm Number(s)” label indicates which building alarms are currently enabled. In this example, Building Alarms 1 and 4 are enabled.
12.5.4Customize Alarm Messages
If Customize Alarm Message (option 2) is selected from the Program Building Alarms menu, you can select a custom message for a building alarm or disable a previously enabled building alarm custom message. When this entry is selected, the following menu is displayed:
Customize Alarm Messages
Enabled on Building Alarm Number(s) 2 3
Enter Building Alarm Number:
This example indicates that there are custom messages enabled for Building Alarms 2 and 3. When a building alarm number is entered, the message being used by the software is displayed (either a custom message or the default message indicated by the list of enabled custom messages). If 1 was entered at the prompt, the following is displayed:
Building Alarm Active Message: Building Alarm 1 (default message)
Enter New Message or <CR> for No Change:
EATON Powerware® 9315 UPS |