INSTALLING THE UPS SYSTEM
Installation Checklist
-All packing materials and restraints have been removed from each cabinet.
-Each cabinet in the UPS system is placed in its final installation location.
-A ground bond is installed between any cabinets that are bolted together.
-All switchboards, conduits, and cables are properly routed to the UPS and auxiliary cabinets.
-All power cables are properly sized and terminated.
-A ground conductor is properly installed.
-If a bypass input neutral connection is used, no other N‐G bonds exist downstream from the UPS.
-Battery cables and harnesses are terminated on E4 and E5.
-Internal battery cabinet connections have been completed (bus bars, plugs, etc.).
-Shunt trip signal wiring is connected from UPS to battery breaker(s).
-Air conditioning equipment is installed and operating correctly.
-The area around the UPS system is clean and dust‐free. (It is recommended that the UPS be installed on a level, sealed concrete pad or floor.)
-Adequate workspace exists around the UPS and other cabinets.
-Adequate lighting is provided around all UPS equipment.
-A 120V service outlet is located within 7.6m (25 ft) of the UPS equipment.
-Each Remote Monitor Panel (RMP) is mounted in its installed location. (OPTIONAL)
-The control wiring for each RMP is terminated inside the UPS cabinet. (OPTIONAL)
-The remote emergency
-Summary alarms and/or building alarms are wired appropriately. (OPTIONAL)
-A Relay Interface Module (RIM) is mounted in its installed location and its wiring is terminated inside the UPS cabinet. (OPTIONAL)
-A remote battery disconnect control is mounted in its installed location and its wiring is terminated inside the UPS and battery cabinets. (OPTIONAL)
-Circuit breakers with adjustable trip mechanisms adjusted to match site requirements.
-Debris shields covering ventilation grills are removed from all cabinets.
-Startup and operational checks are performed by an authorized Eaton Customer Service Engineer.
EATON Powerware® 9315 UPS |