USING FEATURES AND OPTIONS

10.5Optional Supervisory Contact Module

An optional Supervisory Contact Module (SCM) establishes an interface between the Parallel Capacity/Redundant system manufacturer's equipment and the customer's monitor. This interface allows the customer to monitor operational status of the Parallel Capacity/Redundant system equipment. Figure 10‐3 shows the SCM, input connections on TB1, and output connections on TB2.

TB2

Figure 10‐3. SCM

The SCM provides signals for the following indications:

SYSTEM NORMAL

TB2‐1 through TB2‐3

 

 

NO REDUNDANCY

TB2‐4 through TB2‐6

 

 

ON GENERATOR

TB2‐7 through TB2‐9

 

 

BYPASS NOT AVAILABLE

TB2‐10 through TB2‐12

 

 

ON BATTERY

TB2‐13 through TB2‐15

 

 

UPS ALARM

TB2‐16 through TB2‐18

 

 

ON BYPASS

TB2‐19 through TB2‐21

 

 

SHUTDOWN IMMINENT

TB2‐22 through TB2‐24

 

 