
UPS OPERATING INSTRUCTIONS
13.If system is equipped with motor operated breaker CB2, proceed to Step 14; otherwise, proceed to Step 16.
14.Confirm UPS Battery Breaker CB2 has closed by viewing the breaker position on the LCD Mimic screen.
The inverter and output/inverter cooling blowers turn on. When the inverter reaches full voltage, UPS breaker CB3 closes and breaker CB4 opens supplying power to the critical load. It takes less than one minute for the UPS to achieve Normal mode. If UPS is not in Automode, turn the Mode key switch to NORMAL for one second to transfer UPS to Normal mode.
15.Proceed to Step 18.
16.When the UPS Battery Disconnected alarm and notification is received, close UPS Battery Disconnect CB2.
17.On the UPS, turn the Mode key switch to NORMAL for one second.
The inverter and output/inverter cooling blowers turn on. When the inverter reaches full voltage, UPS breaker CB3 closes and breaker CB4 opens supplying power to the critical load. It takes less than one minute for the UPS to achieve Normal mode. If UPS is not in Automode, turn the Mode key switch to NORMAL for one second to transfer UPS to Normal mode.
18.The UPS system is now operating in Normal mode.
9.3Starting the UPS in Bypass Mode
To start the UPS when the inverter output of the UPS is not available and the critical load needs to be energized:
1.Verify that the UPS circuit breakers are set as follows:
UPS Input Breaker (CB1) | OPEN |
|
|
UPS Battery Breaker or Battery Disconnect (CB2) | OPEN |
|
|
UPS Output Breaker (CB3) | OPEN |
|
|
UPS Bypass Breaker (CB4) | OPEN |
|
|
Backfeed Protection Breaker (FBP) | OPEN |
|
|
2.Close the UPS Bypass input feeder circuit breaker. Breakers CB4 and FBP close as soon as charged. If the breakers do not close, turn the Mode key switch to BYPASS for one second.
The critical load is immediately supplied by the bypass source, in Bypass mode, until the inverter turns on and the UPS transfers to Normal mode. The status indicator on the UPS control panel indicates the UPS is in Bypass mode.
3.The UPS system is now operating in Bypass mode. No backup is available.
EATON Powerware® 9315 UPS |